© Copyright, 1999, all rights reserved • Securitron Magnalock Corp., 550 Vista Blvd., Sparks NV 89434, USA Tel: (775) 355-5625 • (800) MAGLOCK • Fax:
Rev. A.1, 10/99 Page- 8 board. The CCS board provides multiple, current limited two Amp outputs on terminals marked P1, P2 etc. The advantage of u
Rev. A.1, 10/99 Page- 9 controlled by the panel zone. Not also that Securitron can supply additional breakered output boards for the power supply (
Rev. A.1, 10/99 Page- 10 FIG. 3: FAIL SAFE LOCK CONNECTIONS MAGNALOCKREDWHITEBLACKTO DC NEGTO DC NEGCOMNCNOTO DC NEG"S" SENSTATSELSELSEL
Rev. A.1, 10/99 Page- 11 TYPE 3 FAIL SAFE This is the most common configuration. The status switch is still present but a remote release switch suc
Rev. A.1, 10/99 Page- 12 FIG. 4: FAIL SECURE LOCK CONNECTIONS TO DC NEGTO DC NEGSELSEL+-LOCKSIMPLE LOCK HOOKUP WITH NO STATUS MONITORING.S AND L TE
Rev. A.1, 10/99 Page- 13 TYPE 1 FAIL SECURE The type 1 drawing is the simplest. It utilizes a fail secure lock controlled directly by the panel wit
Rev. A.1, 10/99 Page- 14 TYPE 4 FAIL SECURE This is the same as Type 3 except that 2 remote switches are used. An example would be an entry card re
Rev. A.1, 10/99 Page- 15 There are a number of things to consider about this drawing. The main point is to show that a powered switching device at
Rev. A.1, 10/99 Page- 16 FIG. 6: FAIL SAFE/FAIL SECURE TIMER CONNECTIONS TO DC NEGSELLOCK+CLOSED WHEN SECURELOCK OR DOOR STATUS SWITCHFAIL SECURER
Rev. A.1, 10/99 Page- 17 "the system is working". When the release switch is used, the indicator will go out which will prompt the indivi
Rev. A.1, 10/99 SECTION 4.3 FAIL SECURE LOCKS--------------------------------------------------------Page 10 If the locks you will be using are fail
Rev. A.1, 10/99 Page- 18 The silence latch is entirely prewired. However, if the panel that has been supplied was ordered without a silence latch,
Rev. A.1, 10/99 Page- 19 The locks may be immediately released by the associated panel toggle. Optionally, a remote release switch may be provided
Rev. A.1, 10/99 Page- 20 Most installations do not require use of the bypass function. Even if there is a local authorized entry or exit device at
Rev. A.1, 10/99 Page- 21 used. An "S" Senstat Magnalock, Touch Sense Bar and MK keyswitch are employed in place of the generic fail safe
Rev. A.1, 10/99 Page- 22 FIG. 11: GENERAL LCP/XDT CONNECTIONS WITH USE OF BYPASS NONCC1C2C3+LSBPFEINRSNCNCNONO0V (NEG)+VRESET (NC)INITIATE (NC)FA
Rev. A.1, 10/99 Page- 23 NONCC1C2C3+LSBPFEINRSNCNCNONO0V (NEG)+VMAGNALOCKSONA-LERTREDBLACK+TOUCHSENSEBARREDWHTMK KEY-SWITCHWHITEREDLEDREDGREENBLACKX
Rev. A.1, 10/99 Page- 24 keyswitch is in the NO position. Be sure that the keyswitch contacts are of adequate capacity to switch all the power of t
Rev. A.1, 10/99 Page- 25 the bypass switch. The remote switch’s NO terminal then connects to the DC negative lock return wire so that the remote sw
Rev. A.1, 10/99 Page- 26 If other options are used in a master/slave installation, they would wire as follows: If the AM option is present, termina
Rev. A.1, 10/99 Page- 27 6.2 MULTIPLE PANEL FAIL SECURE WIRING If fail secure locks are employed and more than one panel is needed to control them,
Rev. A.1, 10/99 Page- 1 SECURITRON LCP SERIES ELECTRIC LOCK CONTROL PANEL INSTALLATION AND OPERATING INSTRUCTIONS 1. DESCRIPTION 1.1 GENERAL The L
Rev. A.1, 10/99 Page- 28 FIGURE 16: ALTERNATELY ENABLED PANEL WIRING COM NCNODPDT KEYSWITCH ON PANEL #1ALTERNATE ACTION+V FROMPOWER SUPPLY+++COM C
Rev. A.1, 10/99 Page- 29 7. DOOR MONITORING (NO ELECTRIC LOCKS) The panel may also be used to monitor doors where no electric locks are installed.
Rev. A.1, 10/99 Page- 30 MAGNACARE® LIMITED LIFETIME WARRANTY SECURITRON MAGNALOCK CORPORATION warrants that it will replace at customer’s request,
Rev. A.1, 10/99 Page- 2 requirements vary with the monitoring scheme and the voltage but figure a worst case of 60 mA per control zone for panel cur
Rev. A.1, 10/99 Page- 3 1.5 AUDIBLE ALARM AND ALARM RESET The red indicator is always accompanied by a Sonalert sounding on the panel. The panel o
Rev. A.1, 10/99 Page- 4 BICOLOR ORANGE: ZONE THAT HAD BEEN IN VIOLATION HAS RESECURED. PRESSING RESET TOGGLE WILL CLEAR CONDITION, CHANGING LAMP TO
Rev. A.1, 10/99 Page- 5 It is, of course, possible to assign a different function to the additional lights. They can be made to illuminate when any
Rev. A.1, 10/99 Page- 6 3. BOARD TERMINAL DESCRIPTIONS Refer to Figure 1 (Panel Board Overview) to see the terminal layout. This section describes
Rev. A.1, 10/99 Page- 7 TERMINALS "Y1, Y2, Y3, Y4": These input terminals are only active if the AM option has been supplied. With the o
Comentarios a estos manuales